User Manual SICLOCK DCFRS Industrial Version
Order No. 2XV9450-1AR48
Version 1.0
7
3 Technical Data
3.1 Interface RS232
For connecting the DCFRS industrial version to the RS232 interface a 9-pole DSUB plug is required. If
on the interface there is a 25-pole DSUB connector for serial interface, then this must be reduced to 9
contacts with the aid of a customary adapter. The interface has the following assignment:
Pin
Name
Function
2
RxD
Demodulated DCF77 reception signal, 1 pulse per second
4
DTR
negative supply voltage, only when reception service is activated
5
GND
Signal ground
7
RTS
positive supply voltage, only when reception service is activated
Table 1: Interface assignment RS 232.
3.2 Interface Antenna
The 4 wires on the split connection of the TTY-RS232 converter have the following function:
Color
Function
yellow
Connecting to the antenna (negative potential)
green
Connecting to the antenna (positive potential)
brown
Supply voltage antenna circuit TTY-RS232 converter connection 1
white
Supply voltage antenna circuit TTY-RS232 converter connection 2
grey
Cable shield
Table 2: Interface assignment antenna connection.
3.3 Antenna
Dimensions (WxHxD): 185 x 80 x 65 mm
Sensitivity:
0,3 µV
Band width:
400 Hz
Type of Protection:
IP 65
Operating temperature:
-10°C to +50°C
3.4 TTY-RS232-Converter
Dimensions (WxHxD):
60 x 30 x 40 mm
3.4.1 RS232-Sender
Supply voltage:
+/- 8V to +/- 15V
Zero signal current:
4 mA
max. Output current:
+/- 25 mA
3.4.2 Line current (TTY)
Supply voltage:
10V AC to 20V AC or 15V DC to 30V DC
Output current:
20 mA
Isolation voltage:
500V
max. cable length:
1000m, 2-wire drilled and shielded lead,
Loop resistance:
less than 150 Ohm.
4 Ordering data
SICLOCK DCFRS industrial version (TTY interface) ..........................................................................................2XV9450-1AR21
SICLOCK Operating manual for DCFRS industrial version (TTY interface) ........................................................2XV9450-1AR48
SICLOCK DCFRS antenna with TTY interface ...................................................................................................2XV9450-1AR16
SICLOCK Reception service for DCF77 for SIMATIC S7 AS300/AS400 ............................................................2XV9450-1AR32
SICLOCK Installation manual for reception service for DCF77 for SIMATIC S7 AS300/AS400 ..........................2XV9450-1AR33
SICLOCK Reception service for Windows 95/98/2000/NT..................................................................................2XV9450-1AR28
SICLOCK Installation manual for reception service for Windows 95/98/2000/NT................................................2XV9450-1AR20