Diagramm Abgleich
Die folgende Abbildung zeigt die Funktion des Abgleichs.
Secondary_value_1
Calibration
Lowest Point
Calibration
Highest Point
Sensor_value
cal_level_lo
cal_level_hi
Calibration
Lowest Point
Calibration
Highest Point
Sensor reference plane
cal_level_lo [%]
cal_level_hi [%]
Abb. 32: Abgleich VEGAFLEX 66
Parameterliste
Die folgende Liste enthält die wichtigsten Parameter und ihre Bedeutung:
l
primary_value
-
This is the process value after adjustment and Linearization with the status of the transducer
block
-
It is the input for the AIFB when CHANNEL = 1 is selected
-
The unit is defined in "primary_value_unit"
l
primary_value_unit
-
Selected unit code for "primary_value"
l
secondary_value_1
-
This is the process value after adjustment with the status of the transducer block
-
It is the input for the AIFB when CHANNEL = 2 is selected
-
The unit is defined in "secondary_value_2_unit"
l
secondary_value_1_unit
-
Selected unit code for "secondary_value_1"