6 konfiguration typischer modbus-hosts, Fehlercodes, Fisher roc 809 – VEGA VEGAFLEX 86 Modbus and Levelmaster protocol Coax probe Benutzerhandbuch
Seite 82: Anschlussplan, Parameter, 11 anhang

82
11 Anhang
VEGAFLEX 86 • Modbus- und Levelmaster-Protokoll
42288-DE-130311
Response:
Parameter
Length
Code/Data
Report Receive to Transmit Delay
7 characters ASCII
UuuRmmm
mmm = milliseconds (50 up to 250),
default = 127 ms
Fehlercodes
Error Code
Name
EE-Error
Error While Storing Data in EEPROM
FR-Error
Erorr in Frame (too short, too long, wrong data)
LV-Error
Value out of limits
11.6 Konfiguration typischer Modbus-Hosts
Fisher ROC 809
Anschlussplan
+
+
power supply
MODBUS
D0
D1
IS GND
USB
B
COM
Z
Y
A
(Rx/Tx -)
(Rx/Tx +)
1
2
3
13
45
2o
ff
on
( )
(
)
(-)
(-)
+8
+30 Vdc
to
GND
Abb. 38: Anschluss des VEGAFLEX 86 an RTU Fisher ROC 809
1 VEGAFLEX 86
2 RTU Fisher ROC 809
3 Spannungsversorgung
Parameter
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
Conversion Code 66
Input Register Base Number
0