5 set number of floats, 5 set baud rate, 5 set receive to transmit delay – VEGA VEGAPULS 66 (≥ 2.0.0 - ≥ 4.0.0) enamel Modbus and Levelmaster protocol Benutzerhandbuch
Seite 71: 5 report number of floats

71
11 Anhang
VEGAPULS 66 Email • Modbus- und Levelmaster-Protokoll
41368-DE-121009
11.5 Set number of Floats
Request:
Parameter
Length
Code/Data
Set number of Floats
5 characters ASCII
UuuFn
Response:
Parameter
Length
Code/Data
Set number of Floats
6 characters ASCII
UuuFOK
Wird die Anzahl auf 0 gesetzt, wird kein Füllstand mehr zurückgemeldet
11.5 Set Baud Rate
Request:
Parameter
Length
Code/Data
Set Baud Rate
8 (12) characters ASCII
UuuBbbbb[b][pds]
Bbbbb[b] = 1200, 9600 (default)
pds = parity, data length, stop bit
(optional)
parity: none = 81, even = 71 (de-
fault), odd = 71
Response:
Parameter
Length
Code/Data
Set Baud Rate
11 characters ASCII
Beispiel: U01B9600E71
Gerät an Adresse 1 ändern zu Baudrate 9600, Parität even, 7 Datenbits, 1 Stoppbit
11.5 Set Receive to Transmit Delay
Request:
Parameter
Length
Code/Data
Set Receive to Transmit Delay
7 characters ASCII
UuuRmmm
mmm = milliseconds (50 bis 250),
default = 127 ms
Response:
Parameter
Length
Code/Data
Set Receive to Transmit Delay
6 characters ASCII
UuuROK
11.5 Report Number of Floats
Request:
Parameter
Length
Code/Data
Set Receive to Transmit Delay
4 characters ASCII
UuuF