EVCO EVK411M Benutzerhandbuch
Seite 2

EVCO S.p.A.
This document belongs to Evco; unless you are authorized by Evco, you can not publish it.
Via Mezzaterra 6, 32036 Sedico Belluno ITALY
Evco does not take any responsibility about features, technical data and possible mistakes related in this document or coming by its use.
Phone +39-0437-852468 • Fax +39-0437-83648
Evco does not take any responsibility about damages coming by the non-observance of the additional information.
[email protected] • www.evco.it
Evco reserves the right to make any change without prior notice and at any time without prejudice the basic safety and operating features.
PT • 43/10
GB ENGLISH
9
WORKING SETPOINTS AND CONFIGURATION PARAMETERS
9.1 Working setpoints
MIN.
MAX.
U.M.
DEF.
WORKING SETPOINTS
r1
r2
°C/°F (1) 0.0
working setpoint
9.2 Configuration parameters
PARAM. MIN.
MAX.
U.M.
DEF.
WORKING SETPOINTS
SP
r1
r2
°C/°F (1) 0.0
working setpoint
PARAM. MIN.
MAX.
U.M.
DEF.
MEASURE INPUTS (2)
CA1
-25.0
25.0
°C/°F (1) 0.0
room probe offset
P0
0
13
- - -
2
kind of probe
0 = PTC
1 = NTC
2 = J
3 = K
4 = 3 wires Pt 100
5 = 2 wires Pt 100
6 = 3 wires Pt 1000
7 = 2 wires Pt 1000
8 = 4-20 mA
9 = 0-20 mA
10 = 2-10 V
11 = 0-10 V
12 = 3 wires Ni 120
13 = 2 wires Ni 120
P1
0
1
- - -
1
if P0 = 0 ... 7 or 12 ... 13, decimal point Celsius
degree
1 = YES
if P0 = 8 ... 11, decimal point position
0 = no decimal point
1 = on the digit of ten
P2
0
2
- - -
0
unit of measure temperature (influential only on LED
Celsius degree and on LED Fahrenheit if
P0 = 8 ... 11) (3) (4)
0 = °C
1 = °F
2 = LED Celsius degree and LED Fahrenheit degree
will remain turned off
P3
-199.0 199.0 points
-20.0
minimum value of the range of the transducer
P4
-199.0 199.0 points
80.0
maximum value of the range of the transducer
P5
0
1
- - -
0
quantity to show during the normal operation
0 = room temperature
1 = working setpoint
PARAM. MIN.
MAX.
U.M.
DEF.
MAIN REGULATOR
r0
0.1
99.0
°C/°F (1) 2.0
working setpoint differential
r1
-199.0 r2
°C/°F (1) 0.0
minimum working setpoint
r2
r1
(5)
°C/°F (1) 350.0 maximum working setpoint
r3
0
1
- - -
0
locking the working setpoint modification (with the
procedure related in paragraph 4.1)
1 = YES
r5
0
1
- - -
(6)
cooling or heating action
0 = cooling
PARAM. MIN.
MAX.
U.M.
DEF.
LOAD PROTECTIONS
C1
0
240
min
0
minimum time between two activations in succes-
sion of the load; also load delay since the end of
the room probe error (7)
C2
0
240
min
0
minimum time the load remains turned off; also load
delay since you turn on the instrument
C3
0
240
s
0
minimum time the load remains turned on
C4
0
240
min
10
time the load remains turned off during the room
probe error; also look at C5
C5
0
240
min
10
time the load remains turned on during the room
probe error; also look at C4
PARAM. MIN.
MAX.
U.M.
DEF.
DEFROST (8)
d0
0
99
h
8
defrost interval (9)
0 = the defrost at intervals will never be activated
d3
0
99
min
0
defrost duration
0 = the defrost will never be activated
d4
0
1
- - -
0
defrost when you turn on the instrument
1 = YES
d5
0
99
min
0
defrost delay when you turn on the instrument (only
if d4 = 1)
d6
0
1
- - -
1
temperature shown during the defrost
0 = room temperature
1 = if to the defrost activation the room tempera-
ture is below “working setpoint + r0”, at most
“working setpoint + r0”; if to the defrost activa-
tion the room temperature is above “working
setpoint + r0”, at most the room temperature
to the defrost activation (10)
PARAM. MIN.
MAX.
U.M.
DEF.
TEMPERATURE ALARMS
A1
-199.0 (5)
°C/°F (1) 0.0
temperature the first temperature alarm is activated;
also look at A3 (11)
A2
0
240
min
0
first temperature alarm delay (12)
A3
0
4
- - -
0
kind of first temperature alarm
0 = alarm not enabled
1 = absolute lower alarm (or A1)
2 = absolute upper alarm (or A1)
3 = lower alarm relative to the working setpoint (or
"working setpoint - A1”; consider A1 without
sign)
4 = upper alarm relative to the working setpoint (or
"working setpoint + A1”; consider A1 without
sign)
A4
0
240
min
0
temperature alarms delay since the working setpoint
modification (12)
A5
-199.0 (5)
°C/°F (1) 0.0
temperature the second temperature alarm is acti-
vated; also look at A7 (11)
A6
0
240
min
0
second temperature alarm delay (12)
A7
0
4
- - -
0
kind of second temperature alarm
0 = alarm not enabled
1 = absolute lower alarm (or A5)
2 = absolute upper alarm (or A5)
3 = lower alarm relative to the working setpoint (or
"working setpoint - A5”; consider A5 without
sign)
4 = upper alarm relative to the working setpoint (or
"working setpoint + A5”; consider A5 without
sign)
PARAM. MIN.
MAX. U.M.
DEF.
SERIAL NETWORK (MODBUS)
LA
1
247
- - -
247
instrument address
Lb
0
3
- - -
2
baud rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud
LP
0
2
- - -
2
parity
0 = none
1 = odd
2 = even
PARAM. MIN.
MAX. U.M.
DEF.
RESERVED
E9
0
1
- - -
1
reserved
(1)
the unit of measure depends on parameter P2
(2)
the related values refer to model EVK411M; in the model EVK411J parameter P0 can be
set to 2 or 3, parameter P2 can be set to 0 or 1 and parameters P3 and P4 are not
available
(3)
set the parameters related to the regulators appropriately after the
modification of the parameter P2
(4)
if parameter P0 has value 0 ... 7 or 12 ... 13 and parameter P2 has value 2, the
instrument will work as if parameter P2 had value 0
(5)
the value depends on parameter P2 (1,300 °C or 1,999 °F)
(6)
the value depends on the instrument code, as follows:
The question mark (?) replaces one field, the asterisk (*) replaces one or
more fields (or no-one); the field C means cooling, the field H means heating
(7)
if parameter C1 has value 0, the delay since the end of the room probe error will
however be 2 min
(8)
if parameter r5 has value 1 (heating action), the defrost functions will not be enabled
(9)
the instrument stores the count of the defrost interval every 30 min; the modification of
parameter d0 has effect since the end of the previous defrost interval or since the
activation of a defrost by hand
(10)
the display restores the normal operation as soon as the defrost ends and the room
temperature falls below the one that has locked the display (or if a temperature alarm
arises)
(11)
the differential depends on parameter P0 (2.0 °C/4 °F if parameter P0 has value 0 ... 7
or 12 ... 13, 2% of P4 - P3 if parameter P0 has value 8 ... 11)
(12)
during the defrost the temperature alarms are not enabled, on condition that they have
arisen after the activation of the defrost.
The instrument must be disposed according to the local legislation about the collection
or electrical and electronic equipment.
Lo strumento deve essere smaltito secondo le normative locali in materia di raccolta
delle apparecchiature elettriche ed elettroniche.
D DEUTSCH
9
BETRIEBSSOLLWERTE UND
KONFIGURATIONSPARAMETER
9.1 Betriebssollwert
BETRIEBSSSOLLWERTE
Betriebssollwert
9.2 Konfigurationsparameter
BETRIEBSSOLLWERTE
Betriebssollwert
MESSEINGÄNGE (2)
Offset Umgebungstemperaturfühler
Fühlertyp
0 = PTC
1 = NTC
2 = J
3 = K
4 = Pt 100 dreiadrige
5 = Pt 100 zweiadrige
6 = Pt 1000 dreiadrige
7 = Pt 1000 zweiadrige
8 = 4-20 mA
9 = 0-20 mA
10 = 2-10 V
11 = 0-10 V
12 = Ni 120 dreiadrige
13 = Ni 120 zweiadrige
ist P0 = 0 ... 7 oder 12 ... 13, Dezimalpunkt Grad
Celsius
1 = SI
ist P0 = 8 ... 11, Position Dezimalpunkt
0 = kein Dezimalpunkt
1 = auf der digit der etwa zehn
Maßeinheit Temperatur (einflußreich nur auf der LED
Grad Celsius und auf der LED Grad Fahrenheit ist
P0 = 8 ... 11) (3) (4)
0 = °C
1 = °F
2 = der LED Grad Celsius und der LED Grad Fah-
renheit wird gelöscht bleiben
Mindestwert der Messumformereichung
Maximalwert der Messumformereichung
Im Normalbetrieb angezeigter Wert
0 = Umgebungstemperatur
1 = Betriebssollwert
HAUPTREGLER
Differenz Betriebssollwert
Betriebsmindestsollwert
Betriebshöchstsollwert
Änderungssperre Betriebssollwerts (mit dem in Punkt
4.1 beschriebenen Verfahren)
1 = SI
Kühl- oder Heizfunktion
0 = Kühlfunktion
ABNEHMERSCHUTZ
Mindestzeit zwischen zei aufeinander folgenden Ein-
schaltvorgängen des Abnehmers; auch Verzöge-
rung des Abnehmers ab Ende Fehler Umgebungs-
temperaturfühler (7).
Mindestzeit, für die der Abnehmer ausgeschaltet
bleibt; auch Verzögerung des Abnehmers nach dem
Einschalten des Geräts.
Mindestzeit, für die der Abnehmer eingeschaltet
bleibt.
Zeit, für die der Abnehmer bei Auftreten eines Feh-
lers des Umgebungstemperaturfühlers ausgeschal-
tet bleibt; siehe auch C5
Zeit, für die der Abnehmer bei Auftreten eines Feh-
lers des Umgebungstemperaturfühlers eingeschal-
tet bleibt; siehe auch C4.
ABTAUVORGANG (8)
Abtauintervall (9)
0 = Abtauen in Intervallen wird nie aktiviert.
Dauer des Abtauvorganges
0 = Abtauvorgang wird nie aktiviert.
Abtauvorgang beim Einschalten des Geräts
1 = JA
Verzögerung des Abtauvorgangs nach dem Ein-
schalten des Geräts (nur wenn d4 = 1)
Während des Abtauvorgangs angezeigte Tempera-
tur:
0 = Umgebungstemperatur
1 = Wenn die Umgebungstemperatur bei
Aktivierung des Abtauvorganges unter dem
„Betriebssollwert +r0“ liegt: max. „Betriebs-
sollwert +r0“; wenn die Umgebungstemperatur
bei Aktivierung des Abtauvorganges über dem
„Betriebssollwert +r0“ liegt: max. Umgebungs-
temperatur zum Zeitpunkt der Aktivierung des
Abtauvorganges (10)
TEMPERATURALARME
Temperatur, bei deren Erreichen der erste
Temperaturalarm ausgelöst wird; siehe auch A3 (11).
Verzögerung, mit der der erste Temperaturalarm
ausgelöst wird (12).
Typ des ersten Temperaturalarms
0 = kein Alarm
1 = absoluter Mindesttemperaturalarm (A1)
2 = absoluter Höchsttemperaturalarm ( A1)
3 = relativer Mindesttemperaturalarm im Verhältnis
zum Betriebssollwert (“Betriebssollwert - A1”; A1
ohne Vorzeichen)
4 = relativer Höchsttemperaturalarm (“Betriebs-
sollwert + A1”; A1 ohne Vorzeichen)
Verzögerung der Temperaturalarme nach Änderung
des Betriebssollwertes (12)
Temperatur, bei deren Erreichen der zweite
Temperaturalarm ausgelöst wird; siehe auch A7 (11).
Verzögerung, mit der der zweite Temperaturalarm
ausgelöst wird (12)
Typ des zweiten Temperaturalarms
0 = kein Alarm
1 = absoluter Mindesttemperaturalarm (A5)
2 = absoluter Höchsttemperaturalarm (A5)
3 = relativer Mindesttemperaturalarm im Verhältnis
zum Betriebssollwert („Betriebssollwert - A5“;
A5 ohne Vorzeichen)
4 = relativer Höchsttemperaturalarm im Verhältnis
zum Betriebssollwert („Betriebssollwert + A5“;
A5 ohne Vorzeichen)
SERIELLES NETZWERK (MODBUS)
Geräteadresse
Baudrate
0 = 2.400 Baud
1 = 4.800 Baud
2 = 9.600 Baud
3 = 19.200 Baud
Parität
0 = keine Parität
1 = ungerade
2 = gerade
RESERVIERT
Reserviert
(1) Die Maßeinheit hängt vom Parameter P2 ab.
(2) die gebrachten wieder Werte beziehen sich
auf das Modell EVK411M; ins Modell EVK411J
der Parameter P0 hat Wert 2 oder 3, der Para-
meter P2 hat Wert 0 oder 1 und die Parameter
sind P3 und P4 nicht verfügbar
(3) Nach Änderung des Parameters P2
müssen die Parameter der Regler kor-
rekt eingestellt werden.
(4) Ist der Parameter P0 auf 0 ... 7 oder auf
12 ... 13 eingestellt und Parameter P2 auf 2
eingestellt, das Gerät wird laufen als ob der
Parameter P2 wurde zu 0 gegliedert
(5) Der Wert ist vom Parameter P2 abhängig
(1.300 °C oder 1.999 °F)
(6) Der Wert hängt wie folgt vom Gerätecode ab:
Jedes Fragezeichen (?) ersetzt ein Feld,
während der Stern (*) für ein oder
mehrere Felder stehen kann (oder
keins); das Feld C steht für Cooling (Kühl-
betrieb), das Feld H für Heating (Heizbetrieb).
(7) Ist der Parameter C1 auf 0 eingestellt, beträgt
die Verzögerung nach behebung des Fehlers
der Umgebungstemperaturfühlers in jedem
Fall 2 min.
(8) Ist der Parameter r5 auf 1 (Heizfunktion) ein-
gestellt, werden die Abtaufunktionen nicht
aktiviert.
(9) Das Gerät speichert die Zählung des Abtau-
intervalls alle 30 min; die Änderung des Para-
met. d0 wirkt sich nach Abschluss des vorher-
gehenden Abtauintervalls oder mit der manu-
ellen Aktivierung eines Abtauvorganges aus.
(10) Das Display schaltet wieder auf Normalbetrieb
wenn die Umgebungstemperatur nach Ab-
schluss des Abtauvorganges unter den Wert
sinkt, der die Sperre verursacht hat (oder nach
Auslösen eines Temperaturalarms).
(11) Der Differenzwert hängt vom Parameter P0 ab
(2,0 °C bzw. 4 °F ist der Parameter P0 auf
0 ... 7 oder auf 12 ... 13 eingestellt, 2% von
P4 - P3 ist der Par. P0 auf 8 ... 11 eingestellt).
(12) Während des Abtauvorganges sind die
Temperaturalarme deaktiviert, sofern sie nach
Start des Vorgangs ausgelöst wurden.
CODICE
EVK411???C*
EVK411??
EVK411???
EVK411???H?*
VALORE
r5 = 0 (per freddo)
r5 = 1 (per caldo)
r5 = 1 (per caldo)
r5 = 1 (per caldo)
CODE
EVK411???C*
EVK411??
EVK411???
EVK411???H?*
VALUE
r5 = 0 (cooling)
r5 = 1 (heating)
r5 = 1 (heating)
r5 = 1 (heating)