Set number of floats, Set baud rate, Set receive to transmit delay – VEGA VEGABAR 87 Modbus and Levelmaster protocol - Operating Instructions Benutzerhandbuch
Seite 71

71
10 Anhang
VEGABAR 87 • Modbus- und Levelmaster-Protokoll
46297-DE-131030
Set number of Floats
Request:
Parameter
Length
Code/Data
Set number of Floats
5 characters ASCII
UuuFn
Response:
Parameter
Length
Code/Data
Set number of Floats
6 characters ASCII
UuuFOK
Wird die Anzahl auf 0 gesetzt, wird kein Füllstand mehr zurückgemeldet
Set Baud Rate
Request:
Parameter
Length
Code/Data
Set Baud Rate
8 (12) characters ASCII
UuuBbbbb[b][pds]
Bbbbb[b] = 1200, 9600 (default)
pds = parity, data length, stop bit
(optional)
parity: none = 81, even = 71 (de-
fault), odd = 71
Response:
Parameter
Length
Code/Data
Set Baud Rate
11 characters ASCII
Beispiel: U01B9600E71
Gerät an Adresse 1 ändern zu Baudrate 9600, Parität even, 7 Datenbits, 1 Stoppbit
Set Receive to Transmit Delay
Request:
Parameter
Length
Code/Data
Set Receive to Transmit Delay
7 characters ASCII
UuuRmmm
mmm = milliseconds (50 up to 250),
default = 127 ms
Response:
Parameter
Length
Code/Data
Set Receive to Transmit Delay
6 characters ASCII
UuuROK