CHAPTER 9 FPS-S1U RACK SPECIFICATIONS

FPS-S1U Instruction Manual

Notes:

*1: The Output of all the FPS1000 modules are connected in parallel in the rack.

*2: For input voltage lower than 100Vac, maximum output power derated by 10% of the power rating.

*3: For cases where conformance to to various safety standards (UL, EN etc.) is required, to be described

as 100-240Vac (50/60Hz).

*4: Remote sensing can compensate up to 1V drop on each load wire.

*5: Not apllicable for units with I

2

C bus option.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

Number of power supply modules (*1)

Maximum output power

(*2)

Input voltage / frequency range

(*3)

Maximum input current (at 100/200Vac)

AC input connector

Output terminals

Remote sensing

(*4)

Parallel operation

Series operation

(*5)

Remote On/Off control

DC_OK signal

AC fail signal

Over Temperature alarm signal

Vout voltage trimming

Auxiliary power supply

Operating temperature

Storage temperature

Operating humidity

Storage humidity

Vibration

Shock

Applicable safety standards

Withstand voltage

Insulation resistance

Weight (Typ)

Size (W*H*D)

Warranty

---

W

---

A

---

---

V

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

Kg

---

Yr

Maximum 3 x FPS1000 modules of the same output voltage rating.

3000

85~265Vac continuous, 47~63Hz, Single phase

12.0/6.0 for each FPS1000 unit installed

FPS-S1U :IEC inlet for each power supply module . FPS-S1U/P :None

Bus-bars.Refer to outline drawing.

Possible.

Possible. Up to 3 racks with max 8 FPS 1000 units of the same voltage and current rating.

Possible. Up to 2 racks of the same voltage and current rating

Separate control for each FPS 1000 unit , By electrical signal or dry contact

ON: 0~0.6V or short. OFF: 2~15V or open.

Separate control for each FPS1000 unit, Open collector signal.

On when Vout >80% +/-5%. Max.sink current: 10mA

Separate control for each FPS1000 unit ,Open collector signal.

Refer to Instruction Manual

Separate control for each FPS1000 unit ,Open collector signal.

Refer to Instruction Manual

Possible, via separate control for each FPS1000 unit .Refer to Instruction Manual.

11.2~12.5VDC.Maximum output current:0.25A*Number of installed FPS1000 units.

0~50

°C: 100% load. Derate 2%/°C, 50°C to 60°C.

-30~85

°C

10~90% RH, no condensation.

10~90% RH, no condensation.

Built to meet ETS 300 019

Built to meet ETS 300 019

UL60950-1, EN60950-1

Input-Output: 3000Vrms, 1min. Input-Ground: 2000Vrms, 1min. Output-Ground:

500Vrms, 1min.

More than 100Mohm at 25

°C and 70% RH. Output-Ground: 500Vdc

3.7

440x44x351mm. Refer to Outline Drawing.

Two Years