2 series operation, Fig 20-3 series operation – TOA Electronics FPS1000-12 Benutzerhandbuch

Seite 53

Advertising
background image

50

(*) Diodes are user supplied

FPS-T1U

FPS-1000 Module A

FPS-1000 Module B

FPS-1000 Module C

J1(A)-12

J3(C)-3

ON/

OFF_1

A

J2(B)-12

J2(B)-3

ON/

OFF_1

B

J3(C)-12

J1(A)-3

ON/

OFF_1

C

LOAD

+V

+S

-S

-V

+S

-S

+V

-V

+V

+S

-S

-V

(*)

(*)

+V

+S

-S

-V

(*)

20.2 Series operation

Up to three FPS1000 with the same output voltage rating can be connected in series to increase the output voltage
or to create a bipolar voltage source. It is recommended to connect diodes in parallel with each output to prevent
reverse voltage in case of failure in one of the power supplies.
Each diode should be rated to at least the power supply rated output voltage and output current.
Refer to Fig 20-3 for a typical series connection of power supplies.

CAUTION

Series operation is not applicable for units with I

2

C bus option.

Fig 20-3 Series operation