10.7.5 Control and monitoring signals connector
Current sharing signal. When FPS-S1U racks are connected in parallel, the CS pins
of the units should be connected to allow current balance between units.
CS
9
Connection for output voltage trimming of FPS1000 unit "C". The voltage can be
trimmed within its range specifications.
V_TRIM_C
10
Return for the following control and supervisory signals: On/Off, DC_OK,
Over_temperature Alarm, AC_Fail, Auxiliary 12V supply. The Signal return is isolated
from the output terminals.
SIGNAL_RETURN
11
17
NC
18
NC
19
NC
Open collector signal, referenced to pin 11 (Signal Return). On when the output voltage
of FPS1000 unit "C” is higher than
≥ 80%+/-5%. The maximum sink current: 10mA
and the maximum external voltage is 15V.
DC_OK_C
12
Positive sensing. The +Sense signal should be connected to the positive terminal of
the load. The +Sense and -Sense leads should be twisted pair to minimize noise pick-
up effect. The maximum load wires drop compensation is 1V/wire.
+SENSE
13
Open collector signal, referenced to pin 11 (Signal Return). On when the input voltage
of FPS1000 unit "B" is
≥85Vrms. The maximum sink current is 10mA, and the maximum
external voltage is 15Vdc.
AC_FAIL_B
14
Turns the output of FPS1000 unit "B" to On and Off by electrical signal or dry contact
between pin 15 and pin 11 (Signal Return). 0~0.6V or Short: On, 2~15V or Open:
Off. The maximum source current is 2.6mA.
ON/OFF_B
15
Open collector signal, referenced to pin 11 (Signal Return). On when the input voltage
of FPS1000 unit "A" is
≥85Vrms. The maximum sink current is 10mA, and the maximum
external voltage is 15Vdc.
AC_FAIL_A
16
Not connected
Not connected
Not connected
Serial Clock used in the I
2
C interface option. Refer to the I
2
C interface description in
the Chapter 7 in this Instruction Manual.
SCL (I
2
C)
20
Serial Data used in the I
2
C interface option. Refer to the I
2
C interface description in
the Chapter 7 in this Instruction Manual.
SDA (I
2
C)
21
Negative sensing. The -Sense signal should be connected to the negative terminal
of the load. The -Sense and +Sense leads should be twisted pair to minimize noise
pick-up effect. The maximum load wires drop compensation is 1V/wire.
-SENSE
22
Open collector signal, referenced to pin 11 (Signal Return). On when the internal temperature
of FPS1000 unit "C" is within safe limit, Off approx 10
°C below Thermal shut down. The
maximum sink current is 10mA and the maximum external voltage is 15V.
TEMP_ALARM_C
23
Open collector signal, referenced to pin 11 (Signal Return). On when the input voltage
of FPS1000 unit "C" is
≥85Vrms. The maximum sink current is 10mA, and the maximum
external voltage is 15Vdc.
AC_FAIL_C
24
Turns the output of FPS1000 unit "C" to On and Off by electrical signal or dry contact
between pin 25 and pin 11 (Signal Return). 0~0.6V or Short: On, 2~15V or Open: Off.
The maximum source current is 2.6mA.
ON/OFF_C
25