CHAPTER 20 PARALLEL AND SERIES OPERATION

20.1 Parallel operation

Up to 3 x FPS-T1U racks with up to 8 x FPS1000 installed units of the same output voltage rating can be connected
in parallel. The built-in Oring diodes on the main output and on the +12V auxiliary voltage in each FPS1000 unit
allow N+1 operation. By connecting the CS signal between the paralleled units, automatic current balance is achieved,
with +/-10% accuracy. For input voltages less than 100Vac, maximum output Power derated by 10% of the Power
rating. Refer to Fig 20-1 for output Power derating in parallel operation.

20.1.1 Parallel operation with Remote sensing
Fig 20-2 shows typical connection of parallel operation with Remote sensing. The CS signal wires should be as short
aspossible and with the same length.

90

100

100

265

Input voltage
(Vrms)

% of rated Power

85

Fig 20-2 Parallel operation with Remote sensing

FPS-T1U Instruction Manual

Fig 20-1