TOA Electronics FPS1000-12 Benutzerhandbuch

Seite 7

Advertising
background image

4

CHAPTER 1 FPS1000 SERIES SPECIFICATIONS

Model

FPS1000 FPS1000 FPS1000

V/I

-24

-32

-48

24

32

48

29

38.4

58

33

26

17.25

40

31

21

V1 (V)
V2 (V)

I1 (A)
I2 (A)

V1

V2

Fig. 1: Rated output current vs output voltage

Vout (V)

I1

Iout (A)

I2

Notes:
*1: For cases where conformance to various safety standards (UL, EN etc.) is required,
to be described as 100-240Vac (50/60Hz).
*2: At 100/200Vac, rated load and 25˚C ambient temperature.
*3: Not applicable for the noise filter inrush current less than 0.2mS.
*4: Measured with JEITA RC-9131A 1:1 probe, 20MHz B.W.
*5: From 85~132Vac or 170~265Vac, constant load.
*6: From No-load to Rated load, constant input voltage. Measured at the sensing point in Remote sense.
*7: Remote sensing can compensate up to 1V drop on each load wire.
*8: Inverter shut down method. Reset by AC voltage recycle or by On/Off control.
*9: Derate Maximum output power by 10% for input voltage less than 100V

RMS

.

*10 For FPS 1000-12/P(S), when used not with FPS-S1U or FPS-T1U

racks, an EMI suppressor clamp should be attached to the AC cable,
as close as possible to the AC inlet, to meet class B.

FPS1000

-12

12

13.2

66
72

1

V

2

V

3

V

4

A

5

W

6

Input voltage / frequency range

(*1)

---

7

Maximum input current (at 100/200Vac)

A

8

---

9

(*2)

%

10

(*3)

A

11

mS

12

(*5)

---

13

(*6)

---

14

(*4)

mV

15

---

16

PPM/

°C

17

(*7)

V

18

(*9)

---

19 Series operation

(*10)

---

20

---

21

(*8)

V

22

---

23

---

24

---

25

---

26

---

27

---

28

---

29

---

30

---

31

---

32

---

33

---

34

---

35

---

36

---

37

---

38

---

39

---

40

---

41

---

42

---

43

mA

44

Kg

45

---

Rated output voltage

12

32

48

FPS1000 SERIES SPECIFICATIONS

FPS1000-12

FPS1000-32

FPS1000-48

Output voltage range

10.5~13.2

28.8~38.4

43~58

Output voltage set point

12+/-1%

32+/-1%

48+/-1%

Maximum output power

864

992

1008

Maximum Output Current (Refer to Fig.1)

72

31

21

85~265Vac continuous, 47~63Hz, Single phase

12.0/6.0

Power Factor (Typ)

>0.98 at 115/230V and maximum output power

Inrush current

Less than 40A

Efficiency (Typ)

84/86%

84/86%

85/88%

Hold-up time

20mS typical at 100Vac input, rated output voltage and less than 80% of rated load.

Maximum line regulation

0.40%

Max load regulation

0.80%

Output Ripple and noise pk-pk

200

250

300

Temperature stability

0.05% of rated Vout for 8hrs after 30min warm-up. Constant line, load and temperature.

Temperature coefficient

200

Remote sensing

Possible. Refer to Instruction Manual.

Parallel operation

Possible. Refer to Instruction Manual.
Possible. Refer to Instruction Manual.

Over current protection

105~125% of maximum output current. Refer to Fig. 1

Over voltage protection

31~34

41.5~45.5

62~66

Over temperature protection

Inverter shut down method, automatic reset.

Remote On/Off control

By electrical signal or dry contact. ON: 0~0.6V or short. OFF: 2~15V or open.

DC OK signal

Open collector signal. On when Vout>80+/-5% rated output. Max.sink current: 10mA

Over-Temp. warning

Open collector signal. Refer to Instruction Manual

AC fail signal

Open collector signal. Refer to Instruction Manual

Auxiliary power supply

11.2~12.5VDC. 0.25A Maximum output current.

Vout voltage trimming

Possible, via Vout Trim pin in the I/O connector. Refer to Instruction Manual.

Front panel indicators

AC OK, DC OK, DC FAIL

I

2

C Interface

Optional. Refer to Instruction Manual.

Operating temperature-models without IEC inlet

models with IEC inlet

0~50

°C: 100% load. Derate 2%/°C, 50°C to 60°C, Derate 2.5%/°C, 60°C to 70°C.

Storage temperature

-30~85

°C

Operating humidity

10~90% RH, no condensation.

Storage humidity

10~95% RH, no condensation.

Cooling

By internal Fans. Variable speed control.

Vibration

Built to meet ETS 300 019

Shock

Built to meet ETS 300 019

Conducted emission

EN55022B, FCC part 15J-B, VCCI-B

Radiated emission

EN55022B, FCC part 15J-B, VCCI-B

Applicable safety standards

UL60950-1, EN60950-1

Withstand voltage

Input-Output: 3000Vrms, 1min. Input-Ground:

2000

Vrms, 1min. Output-Ground: 500Vrms,1min.

Insulation resistance

More than 100Mohm at 25

°C and 70% RH. Output-Ground: 500Vdc

Leakage current

Less Than 1.1mA at 230Vac

Weight (Typ)

2.0

Size (W*H*D)

127x41x290mm. Refer to Outline Drawing.

24

FPS1000-24

21.5~29

24+/-1%

960

40

81/83%

150

14.3~15.7

0~50

°C: 100% load. Derate 2%/°C, 50°C to 60°C.

---

Advertising
Dieses Handbuch ist für die folgenden Produkte bezogen werden: