34 chapter 13 parallel and series operation, 1 parallel operation – TOA Electronics FPS1000-12 Benutzerhandbuch

Seite 37

Advertising
background image

34

CHAPTER 13 PARALLEL AND SERIES OPERATION

13.1 Parallel operation

Up to 3 FPS-S1U racks with up to 8 FPS1000 installed units of the same output voltage rating can be connected
in parallel. The built-in Oring diodes on the main output and on the +12V auxiliary voltage in each FPS1000 unit
allow N+1 operation. By connecting the CS signal between the paralleled units, automatic current balance is achieved,
with +/-10% accuracy. For input voltages less than 100Vac, maximum output Power derated by 10% of the Power
rating. Refer to Fig 13-1 for output Power derating in parallel operation.

Fig 13-2: Parallel operation with Remote sensing

13.1.1 Parallel operation with Remote sensing
Fig13-2 shows typical connection of parallel operation with Remote sensing. The CS signal wires should be as short
aspossible and with the same length.

LOAD

FPS-S1U #1

+V
+S

-S
-V

+S

-S

FPS-S1U #2

+V
+S

-S
-V

+S

-S

+S

-S

FPS-S1U #3

+V
+S

-S
-V

+S

-S

+V

-V

9

CS

11

SIG.
RTN

ON/

OFF

C

ON/

OFF

B

ON/

OFF

A

5 15 25

9

CS

11

SIG.
RTN

ON/

OFF

C

ON/

OFF

B

ON/

OFF

A

5 15 25

9

CS

11

SIG.
RTN

ON/

OFF

C

ON/

OFF

B

ON/

OFF

A

5 15 25

Fig 13-1: Output Power derating at parallel operation

90

100

100

265

Input voltage
(Vrms)

% of rated Power

85