Mpz−...−6−sw – Festo Модуль уставок MPZ Benutzerhandbuch
Seite 2

21 ... 24
41 ... 43, 45
Fig. 1:
Setpoint value setting via external
potentiometers
31 ... 34
35, 11, 13
21 ... 24
41 ... 43, 45
Fig. 2: Setpoint value setting via programmable logic
controller (PLC)
31 ... 34
35, 11, 13
21 ... 24
41 ... 43, 45
Fig. 3:
Setpoint value setting via switch
Setpoint value module
en
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Type: MPZ−1−24DC−SGH−6−SW
1 Method of operation and use
The MPZ−...−6−SW has been designed for generating 6+1
analogue nominal values for Festo proportional valves.
The MPZ−...−6−SW is a setpoint value generator. Six referĆ
ence or setpoint voltages can be preset by means of rotary
potentiometers.
The output of the MPZ−...−6SW provides constantly the
voltage which is actuated via a digital controller.
The nominal values SP1 ... SP6 have priority. SP1 has the
highest, SP6 the lowest priority.
If none of the six nominal value voltages is actuated, the
output will supply the voltage which is specified at the
external input.
2 Conditions of use
Please note
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Only trained personnel with suitable qualification are
allowed to fit and commission in accordance with the
operating instructions.
Malfunctions will occur if the device is not used
correctly. Make sure that the following specifications
are always observed.
ć Compare the maximum values specified in these operĆ
ating instructions with those of your actual application
(e.g. voltage, temperatures, pressure).
ć Take into account the ambient conditions at your
location.
ć Make sure the device is operated with correctly prepaĆ
red compressed air without aggressive media.
ć Please comply with national and local safety laws and
regulations.
ć Remove all transport packing such as protective wax,
foils (polyamide), caps (polyethylene), cardboard boxes
(except for the sealing elements of the pneumatic
connections).
ć The packing is intended for recycling (except for oiled
paper which must be disposed of ).
ć Use the product in its original state. Unauthorized
modification is not permitted.
3 Display and operating elements
Connection 31 ... 34
Connection 35, 11, 13
Connection 21 ... 24
Connection 41 ... 43, 45
1
2
3
4
Connections
31
Activation setpoint value 1 (SP1)
32
Activation setpoint value 2 (SP2)
33
Activation setpoint value 3 (SP3)
34
Activation setpoint value 4 (SP4)
35
Activation setpoint valuet 5 (SP5)
11
Activation setpoint value 6 (SP6)
13
Control line (0 V)
21
Control line (0 V)
22
Ext. setpoint value input (U
W in
= 0 ... 10 V)
23
Control line (+10 V)
24
Screening (PE)
41
Control line (0 V)
42
Setpoint value output (U
W out
)
43
Voltage supply (ć)
45
Voltage supply (+)
Display and operating parts
1
On" LED
1)
(green):Operating status indicator
2
Identification plate
3
Setpoint value potentiometers SP1 ... SP6
4
Setpoint−LEDs
1)
(yellow): value active
1)
LEDs under transparent cover
4 Installation
The setpoint value module can be fitted in any position.
4.1 Mecanical
Fasten the MPZ−...−6−SW as follows:
· Clamp the MPZ to the hat rail (TH 35−7,5 as per DIN
ENĂ60715):
MPZ−...−6−SW
Hat rail
4.2 Electrical
Warning
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Before working on the electric components:
· Switch off the voltage.
Use cables with a cross−sectional area of the core of max.
2.5 mm
2
. Wire up in accordance with connection diaĆ
gramm Fig. 1, Fig. 2 or Fg. 3.
· The screen of the connecting cable to the setpoint
value receiver (e.g. MPZ− ... or MPPE−...) should only be
connected at one end. Screening connection:
At the end nearest to the setpoint value receiver.
· Do not install the lines to an external setpoint value
potentiometer adjacent to main power cables.
· Screening of the lines to external setpoint value setting
devices (e.g. PLC) should only be connected at one end.
Screening connection:
Terminal 24 or earth potential (PE).
5 Commissioning
Please note
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ć If the operating voltage of 30 V DC is exceeded, the
controller will be damaged.
· Ensure that the DC supply voltage is between
20Ă...Ă30 V, otherwise the functioning of the
MPZ−...−6−SW cannot be garanteed.
ć If the setpoint value is set externally:
· Only apply positive voltages between 0 ... +10ĂVĂDC
to the external setpoint value input (terminal 22).
Proceed as follows:
· Advance setpoint value potentiometers SP1 ... SP6
sufficiently far that the currently selected output
voltages U
W
out
are available (connection 42).
6 Operation and function
Please note
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
If two setpoint values are activated at the same time,
the MPZ−...−6−SW will generate the set−point voltage
value of the higher priority (see table).
Setpoint value
Connection no.
for activation
Priority
1
31
1 (highest)
2
32
2
3
33
3
4
34
4
5
35
5
6
11
6
External source
22
7 (lowest)
Warning
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When switching from one setpoint value to another:
· Make sure that the value with the lower priority is
activated,
ć before a preceding setpoint value of higher
priority becomes inactive;
ć until a subsequent setpoint value of higher
priority has become active.
Otherwise, MPZ−...−6WS emits the voltage of the
external setpoint value during the switching process.
7 Notes on malfunction
Fault
Possible cause
Remedy
On LED does not
light up
Operating voltage too
low
Operating voltage
20Ă...Ă30 V DC
g
p
Incorrect polarity
applied
· Wire up correctly
(see connection
diagrams)
With external
nominal value
potentiometer:
No voltage at the
setpoint value
output
(terminal 42)
External potentiometer
not suitable or
defective
· Disconnect
external
potentiometer
· Check resistance
of the external
potentiometer
2,5Ăkġ
Ţ R < 10 kġ
· If necessary,
replace external
potentiometer
With integrated
nominal value
potentiometer :
No voltage at the
Actuating voltage too
low or incorrect
polarity
Activating voltage
DCĂ15 ... 30ĂV
No voltage at the
setpoint value
output
(terminal 42)
External potentiometer
is still connected
· Replace external
potentiometer
8 Dismantling
1. Switch off the operating voltage in order to dismantle
the MPZ−...−6−SW.
2. Disconnect the relevant connections of the
MPZ−...−6−SW.
3. Insert a screwdriver with a blade at least 6 mm wide
into the protruding unlocking nose (see diagram).
4.Insert a screwdriver with a blade at least 6 mm wide
into the protruding unlocking nose (see diagram).
5. Unlock the MPZ−...−6−SW from the hat rail as shown in
the diagram.
6. Swing the MPZ−...−6−SW away from the hat rail.
9 Technical data
MPZ−1−24DC−SGH−6−SW
Mounting position
Any
Protection class EN 60529
IP20
Operating voltage
Protected against incorrect
polarity
20 ... 30 V DC
Output voltage
0 ... 10 V DC
Output current:
Ĉ Switching input inactive
Ĉ Switching input active
Short−circuit resistant
6 mA
27 mA
Power consumption at 24 V
operating voltage
1,5 W
Temperature ranges:
Ĉ Ambient temperature
Ĉ Storage temperature
0 ... +60 °C
−20 ... +70 °C
Supply output to nominal value
setting devices
10 V +6 %
(shor t circuit current 27 mA)
External nominal value input
0 ... 10 V
Input resistance of the external
nominal value input
L 100 kġ
Input resistance of the setpoint
activations
3 kġ
Electromagnetic compatibility
Ĉ EMC interference emission
Ĉ EMC interference immunity
1)
See conformity declaration
} www.festo.com
1)
With nominal value module MPZ−...−6−SW the max. signal cable
length is 30 m and the supply cable length is 10 m
MPZ−...−6−SW
Operating instructions
Original: de