Eliminating faults
Fault
Possible cause
Remedy
Valve slide does not move
No power supply
Check connection of
DC 24 V power supply
No setpoint
Check control unit and
connection
Valve slide stuck
Send MPYE-... to Festo for
servicing
Valve slide oscillates
Power supply too low
Ensure that power supply is
DC 17 ... 30 V
Cable screening not
connected or connected
incorrectly
Connect screening at end of
cable away from valve
Earth loop
Install MPYE-... with
insulation
Cylinder speed too low
Flow cross-section restricted
by connection system used
(swivel fittings)
Use alternative connection
system