Connection of fsk modem / hart, Communicator, Hazardous area – VEGA T32.10-11-30 Benutzerhandbuch

Seite 22: Safe area, Non hazardous area

Advertising
background image

GB

2383336 12/2008 GB/D

22

WIKA Operating Instructions Temperature Transmitter T32.10/11/30

11. Connection of FSK modem / HART

®

Communicator

11.2 Typical connection in hazardous areas (Rail mounting)

11.3 Typical connection in non hazardous areas

HART

®

Communicator

FSK Modem

Transmitter

Hazardous area

power supply

FSK modem

Safe area

3191281.0



1) Alternative connection for FSK
modem or HART Communicator:
2 mm jack at front of case. We
recommend the use of lamellar plug.

HART

®

Communicator

FSK Modem

Transmitter

Non hazardous area

power supply

RL = Resistance for the HART®

Communication

RL min. 20

Ω, max. 1100 Ω

Ensure that the burden is between

250 and 1100 Ω! Add an appropriate

resistance if needed.

1)

The rail mounting version of the T32 enables direct connection for an FSK modem / HART

®

Communicator.

Advertising