VEGA T32.10-11-30 Benutzerhandbuch

Seite 6

Advertising
background image

GB

2383336 12/2008 GB/D

6

WIKA Operating Instructions Temperature Transmitter T32.10/11/30

3. Intended use

Electromagnetic compatibility per EN 61 326 and NAMUR recom-

mendation NE21

Signalling at the analogue output per NAMUR recommendation
NE3
Sensor burnout signalling per NAMUR recommendation NE89

Before initial operation check the suitability for the intended

application.

3.1 Functional description

The temperature transmitter serves for the conversion of a

resistance value or a voltage value into a proportional current signal

( ... 20 mA). The analogue signal is transmitted to a series-

connected logic unit, e.g. an SPS or an alarm contact, where

it is monitored for upper deviations from a maximum value or

lower deviations from a minimum value. For failure monitoring the

logic unit has to be capable of recognising HI alarms (adjustable

from 21 ... 22. mA) as well as LO alarms (3.6 mA). The electrical

components of the transmitter are arranged in a plastic case and
completely encapsulated.

3.2 Ambient conditions

T32.1*.***

T32.3*.***

Ambient/storage
temperature

Standard range
Extended range

-0 ... +8 °C
-0 ... +8 °C

-20 xxx +70 °C
---

Climate class

Cx (-0 ... +8 °C,  %
to 9 % rel. air humidity)
DIN EN 60 6-1

Bx (-20 ... +70 °C,  %
to 9 % rel. air humidity)
DIN EN 60 6-1

Max. permissible
humidity

100 % relative humidity
(unlimited with insulated
sensor connection
wires), moisture conden-
sation permissible
DIN IEC 68-2-30 Var. 2

99 % relative humidity
DIN IEC 68-2-30 Var. 2

Vibration

10 ... 2000 Hz  g DIN IEC 68-2-6

Advertising