16. CSA installation drawing

Notes

1 Install per Canadian ElectricalCode (Part 1) and local codes, as applicable

2 Associated apparatus (barrier) must be entity -certified by CSA, used in an certified configuration and installed in accor

dance with barrier manufac

-

tur

er's instructions. T

ransmitter Vmax must be gr

eater or equal to barrier

Vt or V

oc, T

ransmitter Imax must be gr

eater or equal to barrier It or Isc.

Transmitter Pmax must be gr

eater or equal to barrier P

max

.

Total cable capacitance plus Ci of transmitter shall not exceed Ca of barrier

,

Total cable inductance plus Li of transmitter shall not exceed La of barrier

.

Vmax

>=

Voc or Vt

Imax

>=

Isc or It

Pmax

>=

Pmax (barrier)

Ci + Ccable

<=

Ca

Li + Lcable

<=

La

3 The

following

temperatur

e

ranges

ar

e

allowed

depend

on

temperatur

e

code:

for T32.1X,XXX

for T32,3X.XXX

Temperatur

e

ambient

Temperatur

e

ambient

code

temperatur

e range

code

temperatur

e range

T

-

0 °C to 8

 °C

T

-20 °C to 70 °C

T

-

0 °C to 70 °C

T

-20 °C to 70 °C

T6

-

0 °C to 60 °C

T6

-20 °C to 60 °C

4 Thermometers must be entity -appr

oved by CSA, used in an appr

oved

configuration and installed in accor

dance with thermometer manufactur

er's

instructions. Thermometer Vmax must be gr

eater or equal to transmitter

Voc. Thermometer Imax must be gr

eater or equal to transmitter Isc.

Thermometer Pmax must be gr

eater or equal to transmitter Pmax at output.

Total capacitance of thermometer shall not exceed Ca of transmitter

.

Total inductance of the thermometer shall not excced La of transmitter

.

5 No r

evision to drawing without prior CSA appr

oval.