2 fault code – Festo Генератор вакуума OVEM, дюймовый Benutzerhandbuch
Seite 100

OVEM
100
Festo ć OVEM ć 1004b English
8.2.2
Fault code
Note
There are of course faults with which the diagnosis no longer functions. Please refer to
the chapter Eliminating faults" for further information.
DiagĆ
nostic
stage
Fault
code
Description
Remedy
1
1)
Er34
Evacuation time exceeded in 2 of 5 cycles
Check for leakage
Er36
Pressurization time exceeded in 2 of 5 cycles
Check for leakage
2
2)
Er33
Solenoid valve does not switch or not
correctly.
Plunger does not move, current through
solenoid coil not sufficient, short circuit in
solenoid coil
Press mechanical manual
override several times.
Check supply voltage. If there is
no improvement, the device is
defective.
Send device to Festo.
Er35
The set threshold of the evacuation time is
exceeded double the value in 2 of 5 cycles
Check for leakage
Er37
The set threshold of the pressurization time
is exceeded double the value in 2 of 5 cycles
Check for leakage
Er38
Switching frequency of the air−save function
lies over the limit value 1 Hz
Check for leakage
Possible fault when switching on the
air−save function, switching point not logical
Reset input
3
3)
Er17
4)
Undervoltage in power supply < 15 V
Check the power supply
3
Er01
Device defective
Exchange device
ć
Er02
Ū
Er08
Reserved for extensions
ć
Er13
Ū
Er16
Reserved for extensions
ć
1)
[min] [max] flash synchronously; fault display in SHOW mode (è Tab. 11: )
2)
All segments flash. The smallest current fault number is shown.
3)
Centre row of bar code segments flashes; fault display in SHOW mode (è Tab. 11: )
4)
Outputs are reset automatically (0−signal).
Tab. 15: Fault code of the vacuum generator