Note
The monitoring of the evacuation and pressurization times is deactivated at the factory.
6. Press the EDIT button in order to confirm the value set.
è
[msec], [SP], [max], [_|¯] flash.
7. Set the maximum evacuation time with the UP/DOWN button
(OFF: Monitoring of the evacuation time is deactivated).
8. Press the EDIT button in order to confirm the value set.
è
[msec], [SP], [max], [¯|_] flashes
9. Set the maximum pressurization time with the UP/DOWN button
(OFF: Monitoring of the pressurization time is deactivated).
10. Press the EDIT button in order to confirm the value set.
è
The vacuum generator is in the RUN mode.
6.4
TEACH mode
In the TEACH mode the switching size (switching point or display window) with and without air−save
function as well as the pressurization and evacuation times can be taught.
Note
Before teaching make sure that the desired switch function (window or threshold
comparator) and the desired hysteresis are set in the EDIT mode (è chapter 6.3 EDIT
mode).
Threshold value comparator
Window comparator
The (taught) switching point is derived from the
average value of both teach points. Calculation
formula: If both teach points are the same, the
following applies: SP = TP1 = TP2.
The taught switching window is derived from:
SP
min
= smaller teaching point (TP1 or TP2)
SP
max
= greater teaching point (TP1 or TP2)
Position of the teaching points (example)
Position of the teaching points (example)
Tab. 13: Set the switching variables